9 Genius Tips to Master Transformer Winding Resistance Testing

Transformer Winding Resistance Testing (TWRT) is one of the most essential procedures in the maintenance, commissioning, and troubleshooting of power transformers. It can reveal potential winding issues like loose connections, short circuits, or deteriorating insulation, often before they result in costly failures. In this article, I’ll walk you through nine practical tips that can help you master this vital test, based on years of field experience. These tips are designed for electric power industry workers looking to improve their testing accuracy, efficiency, and transformer reliability.


1. Always Account for Temperature Variations

Why Temperature Matters in Transformer Winding Resistance Testing

Temperature has a direct impact on the resistance of transformer windings, especially in copper or aluminum windings. As temperature increases, resistance also rises, which can lead to misleading results if not properly accounted for. Without compensating for temperature, you might think your transformer has a problem when it doesn’t, or miss an issue that’s masked by cooler ambient conditions.

Temperature Compensation Techniques

There are two main ways to handle temperature compensation: manual calculation or using testers that automatically adjust readings based on the ambient temperature. If you’re using manual methods, you’ll need to correct all your results to a standard reference temperature, typically 20°C, for consistency. This is a tedious but essential step in ensuring reliable results.

Personal Anecdote: I remember a particularly hot summer afternoon where a team performed TWRT on a transformer. The results showed alarmingly high resistance, and the team was ready to declare the transformer faulty. After rechecking with proper temperature compensation, the results fell within the acceptable range. This experience taught me early on never to overlook the importance of temperature compensation.


2. Ensure Proper De-Energization Before Testing

Why Transformers Must Be Completely De-Energized

Transformer Winding Resistance Testing should never be conducted on energized transformers. Testing on live equipment not only risks inaccurate readings but also poses serious safety hazards like electrical arcing or equipment damage. Ensuring the transformer is fully de-energized is a non-negotiable step to protect both personnel and the equipment.

Following Proper Shutdown Procedures

Always follow the necessary de-energization protocols, including checking that all switches and isolators are properly open. Once de-energized, use a multimeter or voltage detector to confirm there is no residual voltage before connecting your test leads.

Personal Anecdote: I once supervised a team that skipped a step in the de-energization process. When they connected the test equipment, a powerful arc occurred, damaging both the transformer and testing equipment. Fortunately, no one was injured, but it was a stark reminder of how dangerous it is to bypass safety protocols.


3. Use the Right Test Leads and Connections

Importance of Solid and Clean Connections

One of the most common sources of inaccurate readings in TWRT comes from poor connections. Loose, dirty, or corroded connections can introduce additional resistance, leading to false results. Ensuring clean and solid connections between the test leads and the transformer terminals is critical for obtaining accurate data.

Tips for Setting Up Solid Connections

Before attaching your test leads, clean the connection points with a wire brush or cloth to remove any oxidation or dirt. Use clamps that ensure a tight fit and minimize movement during the test. Testing your leads for resistance before starting the actual test can also help you verify that they are in good condition and not introducing any unwanted resistance.

Personal Anecdote: I once observed a team misdiagnose a winding problem due to a poor connection between the test lead and the terminal. The reading was skewed, showing higher resistance than expected. After cleaning the terminals and re-securing the leads, the results were accurate, and no winding issue was found.


4. Establish a Baseline for Future Comparisons

The Value of Baseline Readings

Establishing baseline measurements at the time of commissioning or during early tests provides critical data for future comparison. Over time, the transformer’s winding resistance will inevitably change as it ages or sustains wear. Having a reliable baseline allows you to track trends and identify problems early on.

Using Baseline Data to Monitor Degradation

Each time you perform a Transformer Winding Resistance Test during routine maintenance, compare the new results with the baseline readings. A gradual increase in resistance could indicate winding degradation or insulation problems, while sudden changes might point to a more immediate issue, like a loose connection or winding damage.

Personal Anecdote: During a routine maintenance check, I compared new test results against a baseline from five years earlier. The results showed a slight but steady increase in resistance, signaling insulation deterioration. This early detection allowed us to schedule maintenance and avoid a more severe failure down the road.


5. Test After Major Events

Why Event-Triggered Testing is Important

Major events, such as mechanical shocks, electrical faults, or lightning strikes, can cause internal damage to transformer windings even if there is no visible external damage. Performing TWRT immediately after such events can help identify problems before they escalate.

Immediate Testing Can Prevent Larger Failures

After events like these, the windings may shift or insulation may weaken. If left unchecked, these issues could lead to a complete failure. Including TWRT as part of your post-event inspection ensures that any internal damage is detected and addressed early.

Personal Anecdote: After a severe thunderstorm hit a substation I was working at, we performed TWRT on the transformers, even though they appeared fine externally. One transformer showed an increase in winding resistance, leading us to further investigate. It turned out that a lightning-induced surge had weakened the insulation, which we were able to repair before it led to a catastrophic failure.


6. Use Calibrated Equipment to Avoid False Results

The Importance of Equipment Calibration

Transformer Winding Resistance Testing is only as good as the equipment you use. Over time, testing devices can drift out of calibration, which can result in misleading readings. Regular calibration of your equipment is essential to ensure accuracy and reliability.

How to Ensure Equipment is Calibrated

Set a regular calibration schedule and make sure your equipment is certified by a trusted authority. Some equipment even offers built-in calibration checks, which can be useful between more formal recalibrations. Make sure your test leads are included in the calibration process as well.

Personal Anecdote: I once worked on a project where uncalibrated equipment gave us erratic readings. After recalibrating, we discovered the initial readings were far off, which almost led to unnecessary repairs. Since then, I make sure every piece of test equipment is up to date on calibration before every significant test.


7. Analyze Resistance Trends, Not Just Single Readings

The Importance of Long-Term Monitoring

One-off readings from TWRT might not tell you the full story of a transformer’s condition. It’s the changes in resistance over time that provide valuable insights into the health of the transformer. Tracking trends in winding resistance can help identify potential problems before they become critical.

Identifying Dangerous Trends

A gradual increase in resistance over time can indicate winding deterioration, poor insulation, or even thermal issues within the transformer. By analyzing these trends, you can schedule maintenance at the most effective time, avoiding unexpected failures.

Personal Anecdote: I once noticed a gradual increase in resistance over several years in one of our transformers. Though the readings were still within acceptable limits, the trend suggested insulation degradation. We scheduled maintenance in advance, preventing what could have been a costly failure.


8. Test Load Tap Changers Separately

Load Tap Changers and Their Impact on Winding Resistance

Load tap changers (LTCs) are critical components in transformers, responsible for adjusting the voltage output. If there is an issue with the LTC’s contacts, it can introduce additional resistance in the windings, affecting the performance of the transformer.

How to Test Load Tap Changers

When performing TWRT, ensure you test the LTC independently of the main windings. Look for signs of worn contacts or mechanical wear that could increase resistance and reduce efficiency. Catching LTC problems early ensures better transformer performance during voltage adjustments.

Personal Anecdote: During a scheduled maintenance, we found elevated resistance in one phase of a transformer with an LTC. By testing the LTC separately, we discovered worn contacts that were affecting resistance. Replacing them early saved us from a much larger issue during peak demand.


9. Prioritize Safety with Personal Protective Equipment (PPE)

Safety is the First Priority

Performing TWRT involves working around high-voltage equipment, and safety should always be the top concern. Even when the transformer is de-energized, using the proper personal protective equipment (PPE) reduces the risk of injury from unexpected electrical hazards.

PPE Essentials for TWRT

Always wear insulated gloves, face shields, and arc flash-rated clothing when performing Transformer Winding Resistance Testing. This not only protects you from potential electrical hazards but also ensures compliance with safety regulations.

Personal Anecdote: Early in my career, I witnessed an incident where a minor arc flash occurred due to a testing error. Fortunately, the technician was fully equipped with proper PPE, preventing any injuries. This incident reinforced the importance of always suiting up for every job, no matter how routine it seems.


Conclusion

Mastering Transformer Winding Resistance Testing takes attention to detail, proper equipment, and a commitment to safety. By following these nine tips, you can significantly improve the accuracy and reliability of your test results, ensuring that transformers continue to operate safely and efficiently. Whether it’s accounting for temperature, monitoring long-term trends, or ensuring the transformer is properly de-energized, each step plays a vital role in the success of TWRT. These expert insights, drawn from years of experience, will help you become more proficient in your testing procedures, leading to better transformer maintenance and performance.