{"id":4915,"date":"2025-12-24T07:05:59","date_gmt":"2025-12-24T07:05:59","guid":{"rendered":"https:\/\/hvtesttech.com\/?p=4915"},"modified":"2025-12-24T07:06:00","modified_gmt":"2025-12-24T07:06:00","slug":"is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading","status":"publish","type":"post","link":"https:\/\/hvtesttech.com\/ru\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/","title":{"rendered":"Is the deviation within the 0.5% limit? Deciphering the Critical TTR Reading"},"content":{"rendered":"<p>For over twenty years, I\u2019ve stood in substations and plant floors, the hum of transformers in the background, a turns ratio tester in my hand. In that time, one question has sparked more intense discussions than any other: <strong>\u201cThe reading is off by 0.6%. Is this a real fault, or could it be the tester?\u201d<\/strong><\/p>\n\n\n\n<p>The international standards from IEEE and IEC are clear: a maximum deviation of <strong>\u00b10.5%<\/strong> from the nameplate ratio is typically permissible for a transformer in good health. But when your device displays 0.6%, you\u2019re in a critical grey zone. Your next decision\u2014to leave a potentially faulty unit in service or to trigger a costly investigation\u2014hinges on your confidence in that number.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">The High Stakes of a Fraction of a Percent<\/h2>\n\n\n\n<p>Early in my career, I was called to a manufacturing plant experiencing mysterious voltage fluctuations. A routine TTR check on an incoming service transformer with a new, but low-cost, tester showed a 0.65% deviation on one phase. We initially dismissed it as borderline, attributing it to possible test lead contact or instrument error. Weeks later, a progressive winding fault led to an internal flashover and a twelve-hour production shutdown. The cost ran into six figures.<\/p>\n\n\n\n<p>The post-failure forensic analysis confirmed what the initial test had hinted at: a subtle turn-to-turn short. The lesson was brutal. <strong>A deviation beyond 0.5% is not a statistic; it\u2019s a symptom.<\/strong> The real question is whether the symptom belongs to the transformer or is an artifact of your measurement.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Measurement Error vs. Real Fault: A Diagnostic Guide<\/h2>\n\n\n\n<p>When you face a borderline reading, a systematic approach is your best tool. First, you must rule out measurement error.<\/p>\n\n\n\n<p><strong>Common Culprits of False Readings:<\/strong><\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>Poor Lead Contact:<\/strong> Oxidation or grease on test points creates resistance, skewing results. Always clean bushings or terminals thoroughly.<\/li>\n\n\n\n<li><strong>Residual Magnetism:<\/strong> DC currents in the transformer (from previous tests or inrush) can create a magnetic field that distorts the AC test signal from your TTR tester, leading to unstable or inaccurate readings.<\/li>\n\n\n\n<li><strong>Instrument Limitations:<\/strong> A tester with lower accuracy (e.g., \u00b10.3%) may struggle to reliably resolve a 0.6% deviation. Its own margin of error could mean the true value is 0.3% or 0.9%.<\/li>\n<\/ul>\n\n\n\n<p><strong>Indicators of a Genuine Fault:<\/strong><\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>Consistency:<\/strong> A true fault will show a stable, repeatable deviation across multiple tests performed minutes apart.<\/li>\n\n\n\n<li><strong>Phase Comparison:<\/strong> A fault is often isolated to one winding. Comparing all three phases (e.g., AB, BC, CA) is crucial. A uniform, slight deviation across all phases might indicate a systematic error, while a deviation isolated to one phase strongly points to a physical problem.<\/li>\n\n\n\n<li><strong>Diagnostic Corroboration:<\/strong> A real winding fault will often show supporting evidence in other tests, such as increased excitation current or later, dissolved gas analysis (DGA) results.<\/li>\n<\/ul>\n\n\n\n<h2 class=\"wp-block-heading\">The Tool That Cuts Through Doubt: Why Tester Quality is Non-Negotiable<\/h2>\n\n\n\n<p>In the grey zone, your tester must be the one variable you can trust absolutely. This is where the design philosophy of a professional-grade instrument, like the <strong>HV HTRC Series Transformer Turns Ratio Tester<\/strong>, becomes critical.<\/p>\n\n\n\n<p>My confidence in navigating these situations now relies on a tool built to eliminate guesswork:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>High-Precision Core:<\/strong> With a basic accuracy of <strong>0.05%<\/strong>, the HTRC doesn&#8217;t just measure; it resolves. The difference between 0.48% and 0.52% is clear and trustworthy, removing instrument error from the diagnostic equation.<\/li>\n\n\n\n<li><strong>Anti-Interference &amp; Demagnetization:<\/strong> It actively counters the two biggest field-test headaches. Advanced filtering ensures stable readings in electrically noisy substations, and a built-in <strong>demagnetization function<\/strong> erases residual magnetism, guaranteeing you test the transformer, not its magnetic history.<\/li>\n\n\n\n<li><strong>Automated Certainty:<\/strong> The fully automatic test sequence removes operator influence. It applies the signal, calculates ratio, polarity, and phase angle error, and delivers a clear, repeatable result in seconds. This consistency is key when verifying a borderline finding.<\/li>\n<\/ul>\n\n\n\n<h2 class=\"wp-block-heading\">A Real-World Decision: The 0.6% Deviation<\/h2>\n\n\n\n<p>Let me describe a recent case. A utility was commissioning a refurbished 33\/11 kV transformer. Our initial TTR test with the HTRC showed a 0.58% deviation on the \u2018B\u2019 phase. It was <em>barely<\/em> outside the limit, but the reading was rock-solid across five repetitions. The other phases were within 0.1%.<\/p>\n\n\n\n<p>We used the tester\u2019s data logging to capture the result and performed a complementary excitation current test, which also showed an anomaly on the same phase. This multi-test evidence, anchored by the precise and repeatable TTR data, gave us the confidence to recommend further internal inspection. The finding? A slightly mispositioned spacer creating a minor, but real, impedance mismatch in that winding. It was corrected before the transformer ever entered service, preventing a future latent failure.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">The Professional&#8217;s Verdict<\/h2>\n\n\n\n<p>The 0.5% limit is a bright line, but the real world is measured in shades of grey. When your reading is 0.6%, you are not just interpreting a number\u2014you are conducting a forensic investigation. The first step is to ensure your primary tool is not a suspect.<\/p>\n\n\n\n<p>A precision-engineered TTR tester does more than provide a value; it delivers <strong>diagnostic certainty<\/strong>. It transforms a questionable \u201c0.6%\u201d from a source of anxiety into a clear, actionable data point, empowering you to protect critical assets with confidence.<\/p>\n\n\n\n<p><strong>Don&#8217;t let instrument doubt cloud critical decisions.<\/strong><br>Equip your team with the precision that turns borderline data into definitive action. <strong><a href=\"https:\/\/hvtesttech.com\/ru\/transformer-turns-ratio-ttr-testers\/\">Explore the HV HTRC Series Transformer Turns Ratio Tester and see how it delivers the certainty you need.<\/a><\/strong><\/p>\n\n\n\n<p><\/p>","protected":false},"excerpt":{"rendered":"<p>For over twenty years, I\u2019ve stood in substations and plant floors, the hum of transformers in the background, a turns ratio tester in my hand. In that time, one question has sparked more intense discussions than any other: \u201cThe reading is off by 0.6%. Is this a real fault, or could it be the tester?\u201d [&hellip;]<\/p>","protected":false},"author":1,"featured_media":4714,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"om_disable_all_campaigns":false,"_monsterinsights_skip_tracking":false,"_monsterinsights_sitenote_active":false,"_monsterinsights_sitenote_note":"","_monsterinsights_sitenote_category":0,"footnotes":""},"categories":[11],"tags":[],"class_list":["post-4915","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-transformer-testing"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v25.0 - https:\/\/yoast.com\/wordpress\/plugins\/seo\/ -->\n<title>Is the deviation within the 0.5% limit? Deciphering the Critical TTR Reading - HVTestTech \u2013 High Voltage Testing Equipment Experts<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/hvtesttech.com\/ru\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/\" \/>\n<meta property=\"og:locale\" content=\"ru_RU\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Is the deviation within the 0.5% limit? Deciphering the Critical TTR Reading - HVTestTech \u2013 High Voltage Testing Equipment Experts\" \/>\n<meta property=\"og:description\" content=\"For over twenty years, I\u2019ve stood in substations and plant floors, the hum of transformers in the background, a turns ratio tester in my hand. In that time, one question has sparked more intense discussions than any other: \u201cThe reading is off by 0.6%. Is this a real fault, or could it be the tester?\u201d [&hellip;]\" \/>\n<meta property=\"og:url\" content=\"https:\/\/hvtesttech.com\/ru\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/\" \/>\n<meta property=\"og:site_name\" content=\"HVTestTech \u2013 High Voltage Testing Equipment Experts\" \/>\n<meta property=\"article:published_time\" content=\"2025-12-24T07:05:59+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2025-12-24T07:06:00+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/hvtesttech.com\/wp-content\/uploads\/2025\/10\/54.jpg\" \/>\n\t<meta property=\"og:image:width\" content=\"600\" \/>\n\t<meta property=\"og:image:height\" content=\"338\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/jpeg\" \/>\n<meta name=\"author\" content=\"John Roberts\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"\u041d\u0430\u043f\u0438\u0441\u0430\u043d\u043e \u0430\u0432\u0442\u043e\u0440\u043e\u043c\" \/>\n\t<meta name=\"twitter:data1\" content=\"John Roberts\" \/>\n\t<meta name=\"twitter:label2\" content=\"\u041f\u0440\u0438\u043c\u0435\u0440\u043d\u043e\u0435 \u0432\u0440\u0435\u043c\u044f \u0434\u043b\u044f \u0447\u0442\u0435\u043d\u0438\u044f\" \/>\n\t<meta name=\"twitter:data2\" content=\"5 \u043c\u0438\u043d\u0443\u0442\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"WebPage\",\"@id\":\"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/\",\"url\":\"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/\",\"name\":\"Is the deviation within the 0.5% limit? Deciphering the Critical TTR Reading - HVTestTech \u2013 High Voltage Testing Equipment Experts\",\"isPartOf\":{\"@id\":\"https:\/\/hvtesttech.com\/es\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/hvtesttech.com\/wp-content\/uploads\/2025\/10\/54.jpg\",\"datePublished\":\"2025-12-24T07:05:59+00:00\",\"dateModified\":\"2025-12-24T07:06:00+00:00\",\"author\":{\"@id\":\"https:\/\/hvtesttech.com\/es\/#\/schema\/person\/422ac5e84e61a55051982d614d95e28c\"},\"breadcrumb\":{\"@id\":\"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/#breadcrumb\"},\"inLanguage\":\"ru-RU\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"ru-RU\",\"@id\":\"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/#primaryimage\",\"url\":\"https:\/\/hvtesttech.com\/wp-content\/uploads\/2025\/10\/54.jpg\",\"contentUrl\":\"https:\/\/hvtesttech.com\/wp-content\/uploads\/2025\/10\/54.jpg\",\"width\":600,\"height\":338},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\/\/hvtesttech.com\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Is the deviation within the 0.5% limit? Deciphering the Critical TTR Reading\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/hvtesttech.com\/es\/#website\",\"url\":\"https:\/\/hvtesttech.com\/es\/\",\"name\":\"HVTestTech \u2013 High Voltage Testing Equipment Experts\",\"description\":\"Precision Testing Solutions for Electrical Safety and Performance\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/hvtesttech.com\/es\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"ru-RU\"},{\"@type\":\"Person\",\"@id\":\"https:\/\/hvtesttech.com\/es\/#\/schema\/person\/422ac5e84e61a55051982d614d95e28c\",\"name\":\"John Roberts\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"ru-RU\",\"@id\":\"https:\/\/hvtesttech.com\/es\/#\/schema\/person\/image\/\",\"url\":\"https:\/\/secure.gravatar.com\/avatar\/51561face8e05db040d8c4bf07795c74aad101c223419f5c83069fd695a2d790?s=96&d=mm&r=g\",\"contentUrl\":\"https:\/\/secure.gravatar.com\/avatar\/51561face8e05db040d8c4bf07795c74aad101c223419f5c83069fd695a2d790?s=96&d=mm&r=g\",\"caption\":\"John Roberts\"},\"description\":\"I am John Roberts, a professional electrical testing expert with over 35 years of experience in power systems. I specialize in using advanced testing equipment to maintain and improve electrical infrastructure. As a leader and mentor, I guide my team through complex power projects, always prioritizing safety and efficiency. My innovative approach and commitment to team development have earned me respect in the engineering community, establishing me as a trusted authority in electrical testing and power system reliability.\",\"sameAs\":[\"https:\/\/hvtesttech.com\"],\"url\":\"https:\/\/hvtesttech.com\/ru\/author\/salehvtesttech-com\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Is the deviation within the 0.5% limit? Deciphering the Critical TTR Reading - HVTestTech \u2013 High Voltage Testing Equipment Experts","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/hvtesttech.com\/ru\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/","og_locale":"ru_RU","og_type":"article","og_title":"Is the deviation within the 0.5% limit? Deciphering the Critical TTR Reading - HVTestTech \u2013 High Voltage Testing Equipment Experts","og_description":"For over twenty years, I\u2019ve stood in substations and plant floors, the hum of transformers in the background, a turns ratio tester in my hand. In that time, one question has sparked more intense discussions than any other: \u201cThe reading is off by 0.6%. Is this a real fault, or could it be the tester?\u201d [&hellip;]","og_url":"https:\/\/hvtesttech.com\/ru\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/","og_site_name":"HVTestTech \u2013 High Voltage Testing Equipment Experts","article_published_time":"2025-12-24T07:05:59+00:00","article_modified_time":"2025-12-24T07:06:00+00:00","og_image":[{"width":600,"height":338,"url":"https:\/\/hvtesttech.com\/wp-content\/uploads\/2025\/10\/54.jpg","type":"image\/jpeg"}],"author":"John Roberts","twitter_card":"summary_large_image","twitter_misc":{"\u041d\u0430\u043f\u0438\u0441\u0430\u043d\u043e \u0430\u0432\u0442\u043e\u0440\u043e\u043c":"John Roberts","\u041f\u0440\u0438\u043c\u0435\u0440\u043d\u043e\u0435 \u0432\u0440\u0435\u043c\u044f \u0434\u043b\u044f \u0447\u0442\u0435\u043d\u0438\u044f":"5 \u043c\u0438\u043d\u0443\u0442"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"WebPage","@id":"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/","url":"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/","name":"Is the deviation within the 0.5% limit? Deciphering the Critical TTR Reading - HVTestTech \u2013 High Voltage Testing Equipment Experts","isPartOf":{"@id":"https:\/\/hvtesttech.com\/es\/#website"},"primaryImageOfPage":{"@id":"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/#primaryimage"},"image":{"@id":"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/#primaryimage"},"thumbnailUrl":"https:\/\/hvtesttech.com\/wp-content\/uploads\/2025\/10\/54.jpg","datePublished":"2025-12-24T07:05:59+00:00","dateModified":"2025-12-24T07:06:00+00:00","author":{"@id":"https:\/\/hvtesttech.com\/es\/#\/schema\/person\/422ac5e84e61a55051982d614d95e28c"},"breadcrumb":{"@id":"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/#breadcrumb"},"inLanguage":"ru-RU","potentialAction":[{"@type":"ReadAction","target":["https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/"]}]},{"@type":"ImageObject","inLanguage":"ru-RU","@id":"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/#primaryimage","url":"https:\/\/hvtesttech.com\/wp-content\/uploads\/2025\/10\/54.jpg","contentUrl":"https:\/\/hvtesttech.com\/wp-content\/uploads\/2025\/10\/54.jpg","width":600,"height":338},{"@type":"BreadcrumbList","@id":"https:\/\/hvtesttech.com\/is-the-deviation-within-the-0-5-limit-deciphering-the-critical-ttr-reading\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/hvtesttech.com\/"},{"@type":"ListItem","position":2,"name":"Is the deviation within the 0.5% limit? Deciphering the Critical TTR Reading"}]},{"@type":"WebSite","@id":"https:\/\/hvtesttech.com\/es\/#website","url":"https:\/\/hvtesttech.com\/es\/","name":"HVTestTech \u2013 High Voltage Testing Equipment Experts","description":"Precision Testing Solutions for Electrical Safety and Performance","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/hvtesttech.com\/es\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"ru-RU"},{"@type":"Person","@id":"https:\/\/hvtesttech.com\/es\/#\/schema\/person\/422ac5e84e61a55051982d614d95e28c","name":"John Roberts","image":{"@type":"ImageObject","inLanguage":"ru-RU","@id":"https:\/\/hvtesttech.com\/es\/#\/schema\/person\/image\/","url":"https:\/\/secure.gravatar.com\/avatar\/51561face8e05db040d8c4bf07795c74aad101c223419f5c83069fd695a2d790?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/51561face8e05db040d8c4bf07795c74aad101c223419f5c83069fd695a2d790?s=96&d=mm&r=g","caption":"John Roberts"},"description":"I am John Roberts, a professional electrical testing expert with over 35 years of experience in power systems. I specialize in using advanced testing equipment to maintain and improve electrical infrastructure. As a leader and mentor, I guide my team through complex power projects, always prioritizing safety and efficiency. My innovative approach and commitment to team development have earned me respect in the engineering community, establishing me as a trusted authority in electrical testing and power system reliability.","sameAs":["https:\/\/hvtesttech.com"],"url":"https:\/\/hvtesttech.com\/ru\/author\/salehvtesttech-com\/"}]}},"_links":{"self":[{"href":"https:\/\/hvtesttech.com\/ru\/wp-json\/wp\/v2\/posts\/4915","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/hvtesttech.com\/ru\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/hvtesttech.com\/ru\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/hvtesttech.com\/ru\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/hvtesttech.com\/ru\/wp-json\/wp\/v2\/comments?post=4915"}],"version-history":[{"count":1,"href":"https:\/\/hvtesttech.com\/ru\/wp-json\/wp\/v2\/posts\/4915\/revisions"}],"predecessor-version":[{"id":4916,"href":"https:\/\/hvtesttech.com\/ru\/wp-json\/wp\/v2\/posts\/4915\/revisions\/4916"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/hvtesttech.com\/ru\/wp-json\/wp\/v2\/media\/4714"}],"wp:attachment":[{"href":"https:\/\/hvtesttech.com\/ru\/wp-json\/wp\/v2\/media?parent=4915"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/hvtesttech.com\/ru\/wp-json\/wp\/v2\/categories?post=4915"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/hvtesttech.com\/ru\/wp-json\/wp\/v2\/tags?post=4915"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}